| | CDT Series | | | |
| | Carbon Dioxide Sensors | | | | | |
| | Optional Temperature Sensor | | | 
| |
| | | | | | |
| | Single beam dual-wave length non-dispersive infrared (NDIR) | | | |
| | | | | | |
| | Supplied factory calibrated for 0 to 2000 ppm CO2 | | | |
| | | | | | |
| | Output signal: 4-20 mA, 0-5 VDC or 0-10 VDC field selectable | | | |
| | | | | | |
| | Input power: 16 to 35 VDC or 19 to 28 VAC. | | | |
| | Power consumption: 2 watts average; 3.75 watts peak. | | | |
| | | | | | |
| | Accuracy: +/-3% of reading or +/-40 ppm. | | | |
| | | | | | |
| | Pushbuttons for use with integral LCD display or A-449 remote display | | |
| | ● can display CO2 only, temperature only, or CO2 and temperature | | |
| | ● provide menu for relay setpoints, sensor output scaling and more | | |
| | ● used in field calibrating sensor | | | | Model with Integral LCD Display |
| | ● can be locked with internal jumper to prevent tampering | | | | | |
| | | | | | | | |
| | Operating Temperature: 32OF to 122OF (30OC to 50OC). | | | | | |
| | | | | See chart below for temperature sensor codes |
| | | | With | With | Dynacon | Select | Enter | |
| | CO2 Output Signal | Temperature Output Signal | LCD | Relay | Part No. | Price Break | Quantity | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | none | --- | --- | CDT-2W40 | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | 4-20 mA, 0-5 VDC, 0-10VDC | --- | --- | CDT-2W44 | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | NTC Thermistor or RTD | --- | --- | CDT-2W4 | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | none | X | --- | CDT-2W40-LCD | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | 4-20 mA, 0-5 VDC, 0-10VDC | X | --- | CDT-2W44-LCD | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | NTC Thermistor or RTD | X | --- | CDT-2W4-LCD | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | none | --- | X | CDT-2W40-RLY | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | 4-20 mA, 0-5 VDC, 0-10VDC | --- | X | CDT-2W44-RLY | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | NTC Thermistor or RTD | --- | X | CDT-2W4-RLY | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | none | X | X | CDT-2W40-LCD-RLY | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | 4-20 mA, 0-5 VDC, 0-10VDC | X | X | CDT-2W44-LCD-RLY | | | |
| | 4-20 mA, 0-5 VDC, 0-10VDC | NTC Thermistor or RTD | X | X | CDT-2W4-LCD-RLY | | | |
| | | Remote LCD display (plugs into port on sensor) | A-449 | 60.00 | | |
| |  | | | ▼ insert code below for type of temperature sensor | |
| | | | A = 10,000Ω NTC thermistor, type III | | |
| | | | B = 10,000Ω NTC thermistor, type II | | |
| | A-449 Remote | | | C = 3000Ω NTC thermistor | | | |
| | LCD Display | | | D = 100Ω platinum RTD | | | |
| | | | | E = 1000Ω platinum RTD | | | |
| | | | | F = 20,000Ω NTC thermistor | | |
| | | | | | | | | | |