| | | 1831 Low Differential Pressure Switch | |
| | | | | | | DPDT, Manual Reset, No Power Required | |
| | | | | | | | | | | | | |
| | Eliminates common problems associated with typical | | | | | | |
| | high duct static cutout installations | | | | 
| |
| | | | | | | | | |
| | Both relay contacts activate and reset at the same time; | | |
| | removes possibility of lead switch shutting down the fan | | |
| | and preventing the lag switch from sending alarm to BAS | | |
| | | | | | | | | |
| | No electrical power required to operate two SPDT switches; | | |
| | eliminates need for separate power loop and its associated | | |
| | wiring and conduit reducing material and installation costs | | |
| | | | | | | | | |
| | Relay contacts rated 4 amps at 125/250 VAC | | | | | |
| | | | | | | | | | | | | |
| | Dual conduit openings for each control loop | | | | | | | |
| | | | | | | | | | | | | |
| | Maximum pressure: 10 psig (68.9 kP) continuous; | | | | | | |
| | 25 psig (172 kP) surge | | | | | | | |
| | | | | | | | | | | |
| | Temperature limits: -30 to 180OF (-34 to 82OC) | | | | | | | |
| | | | | | | | | | | | | |
| | Mounting bracket included | | | MANUAL RESET OPERATION - ACTIVATE ON INCREASE |
| | | | | | | If differential pressure increases above the setpoint, the two |
| | | | | | | relays are activated and latched so N.O. contacts are closed |
| | | | | | | and N.C. contacts are open. The relay contacts will remain |
| | | | | | | in that condition even if differential pressure decreases below |
| | | | | | | the setpoint until manually deactivated by the reset lever. |
| | | | | | | | | | | | | |
| | | | | | | | | | Dynacon | Price | |
| | Switches | Switch Action | Setpoint Range | Part No. | Each | |
| | 2 SPDT | manual reset, activate on pressure insrease | 2.5" to 9.0" WC | 1831-1-RA-S | 120.00 | |
| | | | | | | | | | | | | |